Brand Name : Huaying
Model Number : HYVA-405
Certification : ISO/CE
Place of Origin : Wuhan
MOQ : 1
Price : Negotiable
Supply Ability : 10 units per week
Packaging Details : Wooden case
Warranty : 1 year free and lifelong maintenance
Typical error : 0.02%
Storage : 8G
Function : CT and PT On-site calibration
Customize service : Provided
Feature : Portable
Portable CT PT transformer Test Set For Transformation Ratio Polarity Gauss
Product name: CT PT Analyzer HYVA-405
Reference Standard
GB 1207-2006, GB 1208-2006 (IEC 60044-1), GB16847-1997 (IEC 60044-6) , IEEE C57.13-1993
HYVA-405 is mainly used to detect on phase error, ratio error, burden and admittance test of CT&PT. In addition, it supports data save and site printing, this can not only omit a lot of troublesome work such as manual voltage regulating, manual record and curve tracing, but also dump testing data through USB interface with USB disk .
Features
★ Wide range, it can do CT test from 50/5 zero-sequence CT to 35000/1 generator CT.
★ Simple operation, all parameters and projects of the transformer are tested with one click
★ Ultra-high measurement precision, Typical ratio measurement error is only 0.02%
★ With powerful data management function, single machine can store more than 5000 groups data.
★ Intelligent assessment, it makes conclusion automatically whether the transformer test is qualified.
★ Strong application software support, make word reports for test result in bulk
★ Complete transformer on-site calibration without standard transformer, strong current power source, and load-box
Technical Parameters:
1 Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
2 Power supply: AC220V±10%, 50/60Hz±10%
3 Voltage output: 0.1~180V (AC)
4 Current output: 0.001~5A(RMS)
5 Power output: 500VA
6 Maximum knee voltage measurement: 45KV
7 Current measurement:
Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
Error: <±0.1%+0.01%FS
8 Voltage measurement:
Range: 0~200V (automatically change range in 1V/10V/70V/200V)
Error: < ±0.1%+0.01%FS
9 Turns ratio measurement:
Range:1~35000
1~2000 error<0.05%
2000~5000 error<0.1%
5000~35000 error<0.2%
10 Phase measurement: error: ±2min; resolution: 0.01min
11 Winding resistance measurement:
Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error: < 0.2%RDG+0.02%FS
Maximum resolution: 0.1mΩ
12 Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
|
13 CT Secondary burden:
Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error: <0.2%RDG+0.02%FS
Maximum resolution: 0.001ohm
14 PT Secondary burden:
Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error :<0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15 PT ratio measurement:
Range: 1~35000
1~10000 error<0.1%
10000~35000 error<0.2%
16 PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%
17 PT phase angle measurement: maximum error < 3min
18 Make evaluation for test results according to selected standards
19 Make word report for test result
20 Make word reports one time for multi-group test records on the PC
21 Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
22 Compare excitation curves with saved excitation curves in the same window
23 Memory capacity: >1000 groups test results
24 Working condition: temperature: -10℃~50℃; moist: ≤90%
|
![]() |